Troubleshooting PDF Email Reports Issues

Troubleshooting - PDF Email Reports not Sending


FactoryWiz monitoring uses uses a utility called CRProcess to send email reports. Sometimes this file is blocked by security and needs unblocking.

Procedure:

  1. Remote Desktop into the FactoryWiz server
  2. Go to folder C:\Program Files\RYM\CNC Monitoring Suite
  3. Right click + properties on CRProcess.exe
  4. Check unblock or click the unblock button under general*.
  5. Apply
  6. Restart the FactoryWiz service called RYM FactoryWiz Poller.
*If you do not see unblock, it is already unblocked.



The next test is to manually run CRProcess.exe to see if that gives an error:

  1. Remote Desktop into the FactoryWiz server
  2. Go to folder C:\Program Files\RYM\CNC Monitoring Suite
  3. Open command line from the address bar by typing CMD into the address bar and hit enter
  4. Type into command line: CRPROCESS 0 and hit enter. This will send the first scheduled auto report
Does it send the report? If yes, please contact us and we will remote into the server.


    • Related Articles

    • DNC License Instructions (Version 20.1 or Above)

      This document covers new installations / lost keys and existing systems adding licenses. Existing systems or if you have already received a license can jump to number 5. Click here to download PDF version with screenshots Open the DNC Client on the ...
    • DNC License Instructions for New Customers (or Wiped Licenses)

      This document covers new installations / lost keys and existing systems adding licenses. Existing systems or if you have already received a license can jump to number 5. Click here to download PDF version with screenshots Open the DNC Client on the ...
    • Move License Form for FactoryWiz DNC

      FactoryWiz License Move Request Print, Sign & Return This request will not be processed until you submit it to Factorywiz via fax or email. You must print this form, sign it and scan the signed form and email it to support@factorywiz.com Full Name ...
    • "DR Signal Off" Alarm (Often Alarm 086 on a Fanuc)

      This alarm occurs when the CNC checks the data ready handshake line (sometimes called DR or DTR) and finds that the device is not ready. There are a few possibilities for this problem depending on how your cables are wired. Verify that your port is ...
    • How to Find COM # for Port

      Troubleshooting: How to find COM # to Assign to a Machine - Right Click on Computer or My Computer and click Properties - Click on Device Manager in upper left column (if XP or earlier, click on Hardware, then find Device Manager button) - Click VIEW ...